MS IEC 61558-2-15:2007
SAFETY OF POWER TRANSFORMERS, POWER SUPPLY UNITS AND SIMILAR - PART 2-15: PARTICULAR REQUIREMENTS FOR ISOLATING TRANSFORMERS FOR THE SUPPLY OF MEDICAL LOCATIONS (IEC 61558-2-15:1999, IDT)
This Malaysian Standard deals with all aspects of safety such as electrical, thermal and mechanical.  This standard applies to stationary, single-phase or polyphase, air-cooled (natural or forced) isolating transformers for the supply of group II medical locations, designed to be permanently connected to the fixed wiring of IT supply system, having a rated supply voltage not exceeding 1 000 V a.c. and rated frequency not exceeding 500 Hz. The rated output shall not be less than 3 kVA and shall not exceed 10 kVA. NOTE 1 – Details of IT supply systems are to be found in IEC 60364-3. NOTE 2 – The wiring rules for group II medical locations are under consideration [1]* . The no-load output voltage and the rated output voltage shall not exceed 250 V a.c. singlephase or polyphase (phase-to-phase voltage). Isolating transformers are used where double or reinforced insulation between circuits is required by the installation rules or by the appliance specification. This standard is appli
Published
• (none)  / (none)  / (none)

PDF

23/05/2019
25
NSC 05 - Generation, Transmission & Distribution of Energy
29.180 
30.00

 Add To Cart